Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

LTR-7 eAir W

This model was replaced by LTR-7 Z on 2020-03-01
Supply
Extract
68 %
63 %
766 m³/h
806 m³/h
100 Pa
100 Pa
190 W
170 W
1.61 kW/(m³/s)
1063 m³/h
1214 m³/h
193 Pa
227 Pa
39 %
51 %

Sounds

Lw
LwA
75.4 dB
73.1 dB(A)
62.2 dB
54.3 dB(A)
64.4 dB
55.5 dB(A)
73.0 dB
70.2 dB(A)

Unit information

Ø 250 mm
1510 mm
720 mm
707 mm
130 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P04 211 0006
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
1053 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
17.0 °C / 28 %RH
77.3 %

Fluid coil W

35/25 °C
internal
12.0 °C / 39 %RH
18.0 °C / 26 %RH
0.029 l/s / 0.9 kPa
35  / 25 °C
Water
R212, kvs 2.50
DN15, TR24-SR
1.54 kW

Annual

Camborne,
Great Britain
75.3 %
18 669 kWh
72 kWh

Ecodesign

911 W/(m³/s)
1415 W/(m³/s)
1135 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.7 °C / 57 %RH
77.3 %

Fluid coil W

35/25 °C
internal
23.7 °C / 57 %RH