Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

Pegasos eAir W-CG

This model was replaced by Pegasos Z on 2020-03-01
Supply
Extract
70 %
67 %
766 m³/h
806 m³/h
100 Pa
100 Pa
188 W
189 W
1.68 kW/(m³/s)
1065 m³/h
1101 m³/h
193 Pa
186 Pa
39 %
37 %

Sounds

Lw
LwA
69.5 dB
55.3 dB(A)
51.3 dB(A)
48.3 dB(A)
72.1 dB
64.6 dB(A)
62.4 dB
52.2 dB(A)
67.7 dB
61.3 dB(A)
76.9 dB
74.8 dB(A)

Unit information

Ø 250 mm
1250 mm
1400 mm
677 mm
203 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P06 211 0007
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread) & DN32
1053 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
84.2 %
EN308

Fluid coil W

35/25 °C
internal
13.0 °C / 37 %RH
18.0 °C / 26 %RH
0.018 l/s / 0.2 kPa
35  / 25 °C
Water
R211, kvs 1.60
DN15, TR24-SR
1.28 kW

Fluid coil CG

7/12 °C
internal
18.0 °C / 26 %RH

Annual

Camborne,
Great Britain
82.0 %
20 336 kWh
1 kWh

Ecodesign

945 W/(m³/s)
1617 W/(m³/s)
1337 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
84.2 %
EN308

Fluid coil W

35/25 °C
internal
23.5 °C / 58 %RH

Fluid coil CG

7/12 °C
internal
15.0 °C / 89 %RH
0.133 l/s / 2.9 kPa
5  / 10 °C
Water
R317, kvs 4.00
DN20, TR24-SR
2.22 kW / 2.95 kW
2.04 kW
0.98 l/h