Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Pegasos eWind W

This model was replaced by Pegasos Z on 2020-03-01
Supply
Extract
68 %
67 %
766 m³/h
806 m³/h
100 Pa
100 Pa
182 W
189 W
1.66 kW/(m³/s)
1087 m³/h
1101 m³/h
201 Pa
186 Pa
42 %
37 %

Sounds

Lw
LwA
69.1 dB
54.9 dB(A)
50.9 dB(A)
47.9 dB(A)
71.4 dB
63.9 dB(A)
62.4 dB
52.2 dB(A)
67.1 dB
60.6 dB(A)
76.9 dB
74.8 dB(A)

Unit information

Ø 250 mm
1250 mm
1400 mm
677 mm
203 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P06 301 0006
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
1048 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
17.0 °C / 28 %RH
77.3 %

Fluid coil W

35/25 °C
internal
12.0 °C / 39 %RH
18.0 °C / 26 %RH
0.023 l/s / 0.3 kPa
35  / 25 °C
Water
R211, kvs 1.60
DN15, TR24-SR
1.54 kW

Annual

Camborne,
Great Britain
75.3 %
18 669 kWh
72 kWh

Ecodesign

928 W/(m³/s)
1415 W/(m³/s)
1135 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.7 °C / 57 %RH
77.3 %

Fluid coil W

35/25 °C
internal
23.7 °C / 57 %RH