Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

LTR-7 Z eAir W

Supply
Extract
72 %
72 %
862 m³/h
907 m³/h
100 Pa
100 Pa
176 W
159 W
1.33 kW/(m³/s)
1210 m³/h
1259 m³/h
197 Pa
193 Pa
40 %
39 %

Unit information

Ø 250 mm
1510 mm
720 mm
707 mm
130 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P04 214 0006
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
1053 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
16.8 °C / 29 %RH
76.3 %

Fluid coil W

35/25 °C
internal
11.8 °C / 40 %RH
18.0 °C / 26 %RH
0.028 l/s / 0.4 kPa
35  / 25 °C
Water
R213, kvs 4.00
DN15, TR24-SR
1.79 kW

Annual

Camborne,
Great Britain
74.4 %
20 747 kWh
117 kWh

Ecodesign

795 W/(m³/s)
1383 W/(m³/s)
1103 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.7 °C / 57 %RH
76.3 %

Fluid coil W

35/25 °C
internal
23.7 °C / 57 %RH