Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

LTR-5 Z eAir E

Supply
Extract
92 %
95 %
663 m³/h
698 m³/h
50 Pa
50 Pa
135 W
136 W
1.40 kW/(m³/s)
716 m³/h
734 m³/h
58 Pa
55 Pa
8 %
5 %

Sounds

Lw
LwA
67.1 dB
53.2 dB(A)
49.2 dB(A)
46.2 dB(A)
81.9 dB
75.8 dB(A)
73.7 dB
60.7 dB(A)
73.5 dB
58.4 dB(A)
84.0 dB
76.8 dB(A)

Unit information

Ø 200 mm
1160 mm
528 mm
523 mm
68 kg
Supply: F7, ePM1 55 %, cassette
Extract: M5, ePM10 60 %, cassette
Right
P19 201 0002
230 V/50 Hz, 1~, 1B16A
Unit: 1/4” (internal thread)
2679 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
84.9 %
EN13141-7

Electric heater E

2000 W internal
18.0 °C / 27 %RH

Annual

Camborne,
Great Britain
81.3 %
17 463 kWh
1 kWh

Ecodesign

1099 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
84.9 %
EN13141-7

Electric heater E

2000 W internal
23.5 °C / 58 %RH