Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Cooling

°C

Pelican HP eAir

This model was replaced by Pelican Z on 2020-02-29
Supply
Extract
73 %
63 %
374 m³/h
374 m³/h
50 Pa
50 Pa
75 W
56 W
1.26 kW/(m³/s)
529 m³/h
636 m³/h
100 Pa
145 Pa
41 %
70 %

Sounds

Lw
LwA
60.1 dB
50.0 dB(A)
46.0 dB(A)
43.0 dB(A)
68.2 dB
65.9 dB(A)
56.5 dB
46.6 dB(A)
56.8 dB
47.0 dB(A)
65.3 dB
62.5 dB(A)

Unit information

Ø 200 mm
998 mm
1270 mm
590 mm
125 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P05 210 0002
230 V/50 Hz, 1~, 1C16A
Unit: 2 x DN32
353 W

DWG

Winter

Heat Exchanger

Standard + HP
0 °C / 90 %RH
87.0 %
18.0 °C / 29 %RH
27.3 kJ/kg / 3.6 g/kg
2.37 kW
0.50 kW
0.00 kW

Annual

Camborne,
Great Britain
87.0 %
13 408 kWh
0 kWh

Ecodesign

814 W/(m³/s)

Summer

Heat Exchanger

Standard + HP
26 °C / 50 %RH
0.0 %
15.0 °C / 99 %RH
41.5 kJ/kg / 10.5 g/kg
13.0 °C / 100 %RH
36.6 kJ/kg / 9.3 g/kg
1.68 kW / 2.08 kW
1.00 kW
0.82 kW