Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Cooling

g/kg

Pegasos HP-E eAir

This model was discontinued on 2019-01-01
Supply
Extract
61 %
63 %
862 m³/h
907 m³/h
100 Pa
100 Pa
171 W
192 W
1.44 kW/(m³/s)
1273 m³/h
1310 m³/h
218 Pa
209 Pa
48 %
44 %

Sounds

Lw
LwA
65.0 dB
51.2 dB(A)
44.2 dB(A)
66.0 dB
58.2 dB(A)
57.0 dB
48.1 dB(A)
59.1 dB
51.9 dB(A)
71.7 dB
69.6 dB(A)

Unit information

Ø 250 mm
1250 mm
1400 mm
677 mm
203 kg
M5 / M5
Right
P06 212 0007
400 V/50 Hz, 3~, 3C16A
Electric duct heater E: 230 V/50 Hz, 1~, 1B16A
Unit: 2 x DN32
6743 W

DWG

Winter

Heat Exchanger

Standard + HP
0 °C / 90 %RH
82.0 %
18.0 °C / 27 %RH
26.7 kJ/kg / 3.4 g/kg
26.9 °C / 15 %RH
35.7 kJ/kg / 3.4 g/kg
1.14 kW
0.19 kW

Electric duct heater E

3000 W duct Ø250
18.0 °C / 27 %RH
230 V/50 Hz, 1~, 1B16A

Annual

Camborne,
Great Britain
74.4 %
21 921 kWh
0 kWh

Ecodesign

735 W/(m³/s)
1184 W/(m³/s)
914 W/(m³/s)

Summer

Heat Exchanger

Standard + HP
26 °C / 50 %RH
0.0 %
14.1 °C / 100 %RH
39.5 kJ/kg / 10.0 g/kg
10.3 °C / 100 %RH
30.0 kJ/kg / 7.8 g/kg
2.56 kW
0.46 l/h
1.60 kW

Electric duct heater E

3000 W duct Ø250
15.0 °C / 94 %RH
0.27 kW
230 V/50 Hz, 1~, 1B16A
Valikko