Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
%
°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C
%

Pandion eAir W-CG

Supply
Extract
59 %
60 %
345 m³/h
363 m³/h
50 Pa
50 Pa
63 W
61 W
1.23 kW/(m³/s)
497 m³/h
534 m³/h
104 Pa
108 Pa
44 %
47 %

Sounds

Lw
LwA
55.1 dB
46.7 dB(A)
39.7 dB(A)
67.1 dB
66.4 dB(A)
52.7 dB
48.1 dB(A)
54.1 dB
48.5 dB(A)
71.3 dB
70.5 dB(A)

Unit information

Ø 160 mm
785 mm
895 mm
543 mm
90 kg
M5 / M5
Right
P07 209 0017
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
Coil: G1/2” (external thread)
353 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
17.6 °C / 27 %RH
79.8 %

Fluid coil W

30/20 °C
internal
12.6 °C / 38 %RH
18.0 °C / 26 %RH
0.008 l/s / 0.2 kPa
35  / 25 °C
0 %
R210, kvs 1.00
DN15, TR24-SR
0.62 kW

Fluid coil CG

7/12 °C
duct Ø200
18.0 °C / 26 %RH

Annual

Camborne,
Great Britain
77.7 %
8 682 kWh
9 kWh

Ecodesign

831 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.6 °C / 58 %RH
79.8 %

Fluid coil W

30/20 °C
internal
23.6 °C / 58 %RH

Fluid coil CG

7/12 °C
duct Ø200
15.0 °C / 89 %RH
0.045 l/s / 2.6 kPa
5  / 10 °C
0 %
R311, kvs 1.60
DN15, TR24-SR
1.01 kW / 1.34 kW
0.91 kW
0.44 l/h
Valikko