Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Plaza eco EDW left

This model was discontinued on 2016-05-31
Supply
Extract
70 %
71 %
171 m³/h
180 m³/h
50 Pa
50 Pa
36 W
37 W
1.46 kW/(m³/s)
258 m³/h
267 m³/h
114 Pa
110 Pa
51 %
48 %

Sounds

Lw
LwA
57.8 dB
43.3 dB(A)
39.3 dB(A)
36.3 dB(A)
64.2 dB
61.5 dB(A)
50.5 dB
45.5 dB(A)
51.9 dB
42.6 dB(A)
63.8 dB
62.3 dB(A)

Unit information

Ø 125 mm
598 mm
630 mm
320 mm
46 kg
Supply: F7, ePM1 55 %, cassette
Extract: M5, Coarse 70 %, cassette
Left
P09 014 0001V
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
249 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
83.6 %
EN308

Fluid coil W

35/25 °C
duct Ø125
13.0 °C / 37 %RH
18.0 °C / 26 %RH
0.004 l/s / 0.4 kPa
35  / 25 °C
Water
R209, kvs 0.63
DN15, TR24-SR
0.28 kW

Annual

Camborne,
Great Britain
81.3 %
4 501 kWh
0 kWh

Ecodesign

1017 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
83.6 %
EN308

Fluid coil W

35/25 °C
duct Ø125
23.5 °C / 58 %RH