Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Cooling

g/kg
°C
°C

Pandion TCG-W

This model was replaced by Svea on 2024-04-18
Supply
Extract
55 %
53 %
241 m³/h
254 m³/h
50 Pa
50 Pa
40 W
32 W
1.02 kW/(m³/s)
443 m³/h
473 m³/h
169 Pa
173 Pa
84 %
86 %

Sounds

Lw
LwA
53.0 dB
44.5 dB(A)
40.5 dB(A)
37.5 dB(A)
65.3 dB
64.6 dB(A)
50.2 dB
44.8 dB(A)
52.5 dB
47.1 dB(A)
66.8 dB
65.7 dB(A)

Unit information

Ø 160 mm
785 mm
895 mm
543 mm
90 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P07 219 0012
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
Coil: G1/2” (external thread)
353 W

DWG

Winter

TwinCoil

7/12 °C
duct Ø200
22.0 °C / 30 %RH
22.0 °C / 30 %RH

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 28 %RH
90.3 %
EN308

Fluid coil CG

7/12 °C
duct Ø200
18.0 °C / 28 %RH
3.5 g/kg

Fluid coil W

30/20 °C
internal
13.0 °C / 38 %RH
18.0 °C / 28 %RH
0.005 l/s / 0.4 kPa
35  / 25 °C
Water
R210, kvs 1.00
DN15, TR24-SR
0.40 kW

Annual

Camborne,
Great Britain
88.1 %
6 876 kWh
0 kWh

Ecodesign

686 W/(m³/s)

Summer

TwinCoil

7/12 °C
duct Ø200
23.0 °C / 40 %RH
15.0 °C / 64 %RH
0.019 l/s / 1.4 kPa
5  / 10 °C
Water
R311, kvs 1.60
DN15, TR24-SR
0.69 kW / 0.75 kW
0.07 l/h

Heat Exchanger

Standard
26 °C / 50 %RH
16.0 °C / 92 %RH
90.3 %
EN308

Fluid coil CG

7/12 °C
duct Ø200
14.5 °C / 97 %RH
10.0 g/kg
0.007 l/s / 0.5 kPa
5  / 10 °C
Water
R311, kvs 1.60
DN15, TR24-SR
0.12 kW / 0.22 kW
0.67 kW
0.13 l/h

Fluid coil W

30/20 °C
internal
14.5 °C / 97 %RH