Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

LTR-3 eAir E-CG

Supply
Extract
71 %
71 %
258 m³/h
272 m³/h
50 Pa
50 Pa
46 W
39 W
1.12 kW/(m³/s)
367 m³/h
380 m³/h
101 Pa
98 Pa
42 %
40 %

Sounds

Lw
LwA
60.0 dB
46.5 dB(A)
42.5 dB(A)
39.5 dB(A)
88.0 dB
69.3 dB(A)
73.3 dB
58.2 dB(A)
73.0 dB
58.6 dB(A)
87.0 dB
70.4 dB(A)

Unit information

Ø 160 mm
833 mm
510 mm
480 mm
52 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P02 212 0003
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
Coil: G1/2” (external thread)
749 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
17.6 °C / 27 %RH
79.9 %

Electric heater E

500 W internal
18.0 °C / 27 %RH
0.04 kW

Fluid coil CG

7/12 °C
duct Ø200
18.0 °C / 27 %RH

Annual

Camborne,
Great Britain
77.8 %
6 500 kWh
7 kWh

Ecodesign

773 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.6 °C / 58 %RH
79.9 %

Electric heater E

500 W internal
23.6 °C / 58 %RH

Fluid coil CG

7/12 °C
duct Ø200
15.0 °C / 89 %RH
0.030 l/s / 2.2 kPa
5  / 10 °C
Water
R311, kvs 1.60
DN15, TR24-SR
0.75 kW / 1.00 kW
0.68 kW
0.33 l/h