Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Cooling

°C

Pelican Z HP-E eAir

Supply
Extract
62 %
61 %
374 m³/h
374 m³/h
50 Pa
50 Pa
45 W
46 W
0.88 kW/(m³/s)
616 m³/h
619 m³/h
136 Pa
137 Pa
65 %
65 %

Sounds

Lw
LwA
55.4 dB
43.8 dB(A)
39.8 dB(A)
36.8 dB(A)
73.8 dB
67.9 dB(A)
62.9 dB
46.2 dB(A)
65.0 dB
50.8 dB(A)
76.8 dB
68.9 dB(A)

Unit information

Ø 200 mm
998 mm
1270 mm
590 mm
125 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P05 212 0003
230 V/50 Hz, 1~, 1C16A
Electric duct heater E: 230 V/50 Hz, 1~, 1B16A
Unit: 2 x DN32
3343 W

DWG

Winter

Heat Exchanger

Standard + HP
0 °C / 90 %RH
87.0 %
18.0 °C / 29 %RH
27.3 kJ/kg / 3.6 g/kg
2.37 kW
0.50 kW
0.00 kW

Electric duct heater E

3000 W duct Ø200
18.0 °C / 29 %RH
230 V/50 Hz, 1~, 1B16A

Annual

Camborne,
Great Britain
87.0 %
9 219 kWh
0 kWh

Ecodesign

555 W/(m³/s)

Summer

Heat Exchanger

Standard + HP
26 °C / 50 %RH
0.0 %
15.0 °C / 99 %RH
41.5 kJ/kg / 10.5 g/kg
13.0 °C / 100 %RH
36.6 kJ/kg / 9.3 g/kg
1.68 kW / 2.08 kW
1.00 kW
0.64 kW

Electric duct heater E

3000 W duct Ø200
15.0 °C / 99 %RH
230 V/50 Hz, 1~, 1B16A