Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

LTR-7 XL eWind E

This model was replaced by LTR-7 Z on 2020-05-01
Supply
Extract
65 %
61 %
814 m³/h
857 m³/h
100 Pa
100 Pa
179 W
159 W
1.42 kW/(m³/s)
1154 m³/h
1291 m³/h
201 Pa
227 Pa
42 %
51 %

Sounds

Lw
LwA
71.6 dB
68.5 dB(A)
59.4 dB
50.5 dB(A)
62.6 dB
52.3 dB(A)
68.7 dB
65.5 dB(A)

Unit information

Ø 250 mm
1510 mm
720 mm
707 mm
130 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P04 301 0102
400 V/50 Hz, 3~, 3B10A
Unit: 1/4” (internal thread)
5098 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
83.6 %
EN308

Electric heater E

4000 W internal
18.0 °C / 27 %RH

Annual

Camborne,
Great Britain
81.3 %
21 439 kWh
1 kWh

Ecodesign

829 W/(m³/s)
1595 W/(m³/s)
1315 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
83.6 %
EN308

Electric heater E

4000 W internal
23.5 °C / 58 %RH