Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

LTR-7 XL eAir W-CG

This model was replaced by LTR-7 Z on 2020-05-01
Supply
Extract
68 %
61 %
814 m³/h
857 m³/h
100 Pa
100 Pa
196 W
159 W
1.49 kW/(m³/s)
1091 m³/h
1291 m³/h
180 Pa
227 Pa
34 %
51 %

Sounds

Lw
LwA
72.8 dB
69.6 dB(A)
59.4 dB
50.5 dB(A)
63.8 dB
53.2 dB(A)
68.7 dB
65.5 dB(A)

Unit information

Ø 250 mm
1510 mm
720 mm
707 mm
130 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P04 211 0107
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
Coil: G1/2” (external thread)
1103 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
16.9 °C / 29 %RH
76.8 %

Fluid coil W

35/25 °C
internal
11.9 °C / 40 %RH
18.0 °C / 26 %RH
0.026 l/s / 0.4 kPa
35  / 25 °C
Water
R213, kvs 4.00
DN15, TR24-SR
1.66 kW

Fluid coil CG

7/12 °C
duct Ø315
18.0 °C / 26 %RH

Annual

Camborne,
Great Britain
74.8 %
19 720 kWh
92 kWh

Ecodesign

876 W/(m³/s)
1399 W/(m³/s)
1119 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.7 °C / 57 %RH
76.8 %

Fluid coil W

35/25 °C
internal
23.7 °C / 57 %RH

Fluid coil CG

7/12 °C
duct Ø315
15.0 °C / 89 %RH
0.150 l/s / 10.2 kPa
5  / 10 °C
Water
R313, kvs 4.00
DN15, TR24-SR
2.42 kW / 3.21 kW
2.17 kW
1.06 l/h