Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C

Summer

°C
%RH
°C
%RH

Cooling

°C

Pegasos HP-W eAir

This model was replaced by Pegasos Z on 2019-01-01
Supply
Extract
67 %
62 %
814 m³/h
857 m³/h
100 Pa
100 Pa
191 W
175 W
1.54 kW/(m³/s)
1122 m³/h
1285 m³/h
190 Pa
225 Pa
38 %
50 %

Sounds

Lw
LwA
65.8 dB
51.9 dB(A)
47.9 dB(A)
44.9 dB(A)
68.7 dB
61.1 dB(A)
56.7 dB
47.7 dB(A)
61.1 dB
54.0 dB(A)
71.3 dB
69.2 dB(A)

Unit information

Ø 250 mm
1250 mm
1400 mm
677 mm
203 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P06 212 0008
400 V/50 Hz, 3~, 3C16A
Unit: 2 x DN32
1143 W

DWG

Winter

Heat Exchanger

Standard + HP
0 °C / 90 %RH
83.6 %
18.0 °C / 27 %RH
26.7 kJ/kg / 3.4 g/kg
5.00 kW
1.09 kW
0.00 kW

Fluid coil W

CWW 250-2-2.5
duct Ø250
18.0 °C / 27 %RH

Annual

Camborne,
Great Britain
81.3 %
20 908 kWh
0 kWh

Ecodesign

895 W/(m³/s)
1599 W/(m³/s)
1319 W/(m³/s)

Summer

Heat Exchanger

Standard + HP
26 °C / 50 %RH
0.0 %
15.0 °C / 99 %RH
41.5 kJ/kg / 10.5 g/kg
13.0 °C / 100 %RH
36.6 kJ/kg / 9.3 g/kg
3.65 kW / 4.53 kW
2.18 kW
1.40 kW

Fluid coil W

CWW 250-2-2.5
duct Ø250
15.0 °C / 99 %RH