Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

Pandion eAir E-CG

Supply
Extract
54 %
52 %
241 m³/h
254 m³/h
50 Pa
50 Pa
39 W
31 W
0.99 kW/(m³/s)
450 m³/h
479 m³/h
174 Pa
178 Pa
87 %
89 %

Sounds

Lw
LwA
52.7 dB
44.1 dB(A)
40.1 dB(A)
37.1 dB(A)
64.9 dB
64.2 dB(A)
49.9 dB
44.3 dB(A)
52.1 dB
46.7 dB(A)
66.1 dB
65.0 dB(A)

Unit information

Ø 160 mm
785 mm
895 mm
543 mm
90 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P07 209 0013
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread) & DN32
1153 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 28 %RH
90.3 %
EN308

Electric heater E

800 W internal
18.0 °C / 28 %RH

Fluid coil CG

7/12 °C
internal
18.0 °C / 28 %RH

Annual

Camborne,
Great Britain
88.1 %
6 876 kWh
0 kWh

Ecodesign

667 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.3 °C / 59 %RH
90.3 %
EN308

Electric heater E

800 W internal
23.3 °C / 59 %RH

Fluid coil CG

7/12 °C
internal
15.0 °C / 89 %RH
0.021 l/s / 2.2 kPa
5  / 10 °C
Water
R311, kvs 1.60
DN15, TR24-SR
0.68 kW / 0.90 kW
0.63 kW
0.30 l/h