Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

LTR-7 eAir E-CG

This model was replaced by LTR-7 Z on 2020-03-01
Supply
Extract
68 %
63 %
766 m³/h
806 m³/h
100 Pa
100 Pa
191 W
170 W
1.61 kW/(m³/s)
1060 m³/h
1214 m³/h
192 Pa
227 Pa
38 %
51 %

Sounds

Lw
LwA
75.4 dB
73.1 dB(A)
62.2 dB
54.3 dB(A)
64.5 dB
55.6 dB(A)
73.0 dB
70.2 dB(A)

Unit information

Ø 250 mm
1510 mm
720 mm
707 mm
130 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P04 211 0003
400 V/50 Hz, 3~, 3B10A
Unit: 1/4” (internal thread)
Coil: G1/2” (external thread)
5053 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
84.2 %
EN308

Electric heater E

4000 W internal
18.0 °C / 27 %RH

Fluid coil CG

7/12 °C
duct Ø250
18.0 °C / 27 %RH

Annual

Camborne,
Great Britain
82.0 %
20 336 kWh
1 kWh

Ecodesign

914 W/(m³/s)
1617 W/(m³/s)
1337 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
84.2 %
EN308

Electric heater E

4000 W internal
23.5 °C / 58 %RH

Fluid coil CG

7/12 °C
duct Ø250
15.7 °C / 87 %RH
0.130 l/s / 9.9 kPa
5  / 10 °C
Water
R313, kvs 4.00
DN15, TR24-SR
2.04 kW / 2.62 kW
1.87 kW
0.78 l/h