Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
%
°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C
%

LTR-3 eAir W-CG

This model was discontinued on 2018-01-01
Supply
Extract
67 %
68 %
258 m³/h
272 m³/h
50 Pa
50 Pa
45 W
47 W
1.22 kW/(m³/s)
377 m³/h
389 m³/h
107 Pa
102 Pa
46 %
43 %

Sounds

Lw
LwA
59.3 dB
45.5 dB(A)
38.5 dB(A)
86.9 dB
68.8 dB(A)
72.3 dB
57.7 dB(A)
71.9 dB
57.0 dB(A)
86.1 dB
69.4 dB(A)

Unit information

Ø 160 mm
833 mm
510 mm
480 mm
52 kg
M5 / M5
Right
P02 212 0007
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
Coil: G1/2” (external thread)
249 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
17.6 °C / 27 %RH
79.9 %

Fluid coil W

35/25 °C
duct Ø160
12.6 °C / 38 %RH
18.0 °C / 26 %RH
0.006 l/s / 0.3 kPa
35  / 25 °C
0 %
R209, kvs 0.63
DN15, TR24-SR
0.46 kW

Fluid coil CG

7/12 °C
duct Ø200
18.0 °C / 26 %RH

Annual

Camborne,
Great Britain
77.8 %
6 500 kWh
7 kWh

Ecodesign

733 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.6 °C / 58 %RH
79.9 %

Fluid coil W

35/25 °C
duct Ø160
23.6 °C / 58 %RH

Fluid coil CG

7/12 °C
duct Ø200
15.0 °C / 89 %RH
0.025 l/s / 0.9 kPa
5  / 10 °C
0 %
R311, kvs 1.60
DN15, TR24-SR
0.75 kW / 1.00 kW
0.68 kW
0.33 l/h
Valikko