Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
%
°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C
%

Pegasos eAir W-CG

Supply
Extract
64 %
65 %
718 m³/h
756 m³/h
100 Pa
100 Pa
158 W
167 W
1.55 kW/(m³/s)
1061 m³/h
1083 m³/h
219 Pa
205 Pa
48 %
43 %

Sounds

Lw
LwA
68.1 dB
53.9 dB(A)
46.9 dB(A)
70.1 dB
62.3 dB(A)
61.8 dB
51.5 dB(A)
65.5 dB
58.8 dB(A)
76.1 dB
74.0 dB(A)

Unit information

Ø 250 mm
1250 mm
1400 mm
677 mm
203 kg
M5 / M5
Right
P06 211 0007
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread) & DN32
1053 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
17.1 °C / 28 %RH
77.8 %

Fluid coil W

35/25 °C
internal
12.1 °C / 39 %RH
18.0 °C / 26 %RH
0.018 l/s / 0.1 kPa
35  / 25 °C
0 %
R211, kvs 1.60
DN15, TR24-SR
1.42 kW

Fluid coil CG

7/12 °C
internal
18.0 °C / 26 %RH

Annual

Camborne,
Great Britain
75.8 %
17 613 kWh
54 kWh

Ecodesign

710 W/(m³/s)
1231 W/(m³/s)
961 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.7 °C / 57 %RH
77.8 %

Fluid coil W

35/25 °C
internal
23.7 °C / 57 %RH

Fluid coil CG

7/12 °C
internal
15.0 °C / 89 %RH
0.094 l/s / 1.1 kPa
5  / 10 °C
0 %
R317, kvs 4.00
DN20, TR24-SR
2.13 kW / 2.83 kW
1.92 kW
0.94 l/h
Valikko