Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

LTR-7 Z eAir W-CG

Supply
Extract
72 %
72 %
862 m³/h
907 m³/h
100 Pa
100 Pa
180 W
159 W
1.35 kW/(m³/s)
1199 m³/h
1259 m³/h
193 Pa
193 Pa
39 %
39 %

Sounds

Lw
LwA
64.1 dB
56.8 dB(A)
52.8 dB(A)
49.8 dB(A)
81.6 dB
74.3 dB(A)
73.5 dB
60.7 dB(A)
73.4 dB
60.8 dB(A)
86.4 dB
80.6 dB(A)

Unit information

Ø 250 mm
1510 mm
720 mm
707 mm
130 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P04 214 0007
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
Coil: G1/2” (external thread)
1053 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
82.9 %
EN308

Fluid coil W

35/25 °C
internal
13.0 °C / 37 %RH
18.0 °C / 26 %RH
0.022 l/s / 0.3 kPa
35  / 25 °C
Water
R213, kvs 4.00
DN15, TR24-SR
1.44 kW

Fluid coil CG

7/12 °C
duct Ø315
18.0 °C / 26 %RH

Annual

Camborne,
Great Britain
80.7 %
22 516 kWh
3 kWh

Ecodesign

806 W/(m³/s)
1573 W/(m³/s)
1293 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
82.9 %
EN308

Fluid coil W

35/25 °C
internal
23.5 °C / 58 %RH

Fluid coil CG

7/12 °C
duct Ø315
15.0 °C / 89 %RH
0.163 l/s / 11.8 kPa
5  / 10 °C
Water
R313, kvs 4.00
DN15, TR24-SR
2.52 kW / 3.35 kW
2.30 kW
1.12 l/h