Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

Pegasos Z eAir E-CG

Supply
Extract
58 %
58 %
670 m³/h
706 m³/h
100 Pa
100 Pa
97 W
97 W
0.99 kW/(m³/s)
1197 m³/h
1233 m³/h
319 Pa
305 Pa
79 %
75 %

Sounds

Lw
LwA
58.8 dB
50.8 dB(A)
46.8 dB(A)
43.8 dB(A)
78.6 dB
69.5 dB(A)
66.8 dB
54.5 dB(A)
66.7 dB
54.5 dB(A)
81.2 dB
73.8 dB(A)

Unit information

Ø 250 mm
1250 mm
1400 mm
677 mm
203 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P06 214 0103
400 V/50 Hz, 3~, 3C16A
Unit: 1/4” (internal thread) & DN32
4813 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
85.7 %
EN308

Electric heater E

4000 W internal
18.0 °C / 27 %RH

Fluid coil CG

7/12 °C
internal
18.0 °C / 27 %RH

Annual

Camborne,
Great Britain
83.4 %
18 094 kWh
0 kWh

Ecodesign

521 W/(m³/s)
1662 W/(m³/s)
1382 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.4 °C / 58 %RH
85.7 %
EN308

Electric heater E

4000 W internal
23.4 °C / 58 %RH

Fluid coil CG

7/12 °C
internal
15.0 °C / 89 %RH
0.099 l/s / 2.1 kPa
5  / 10 °C
Water
R317, kvs 4.00
DN20, TR24-SR
1.94 kW / 2.59 kW
1.79 kW
0.87 l/h