Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

Pelican Z eWind E-CG

Supply
Extract
65 %
66 %
428 m³/h
451 m³/h
50 Pa
50 Pa
62 W
61 W
0.98 kW/(m³/s)
640 m³/h
669 m³/h
112 Pa
110 Pa
50 %
48 %

Sounds

Lw
LwA
55.9 dB
44.6 dB(A)
40.6 dB(A)
37.6 dB(A)
74.3 dB
68.8 dB(A)
65.2 dB
47.8 dB(A)
66.4 dB
51.6 dB(A)
77.5 dB
69.7 dB(A)

Unit information

Ø 200 mm
998 mm
1270 mm
590 mm
125 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
230 V/50 Hz, 1~, 1B16A
Unit: 1/4” (internal thread) & DN32
2338 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
17.6 °C / 27 %RH
79.9 %

Electric heater E

2000 W internal
18.0 °C / 27 %RH
0.06 kW

Fluid coil CG

7/12 °C
internal
18.0 °C / 27 %RH

Annual

Camborne,
Great Britain
77.8 %
10 787 kWh
11 kWh

Ecodesign

680 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.6 °C / 58 %RH
79.9 %

Electric heater E

2000 W internal
23.6 °C / 58 %RH

Fluid coil CG

7/12 °C
internal
15.0 °C / 89 %RH
0.077 l/s / 2.3 kPa
5  / 10 °C
Water
R313, kvs 4.00
DN15, TR24-SR
1.25 kW / 1.66 kW
1.13 kW
0.55 l/h