Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

LTR-7 XL eWind W

This model was replaced by LTR-7 Z on 2020-05-01
Supply
Extract
67 %
61 %
814 m³/h
857 m³/h
100 Pa
100 Pa
191 W
159 W
1.47 kW/(m³/s)
1108 m³/h
1291 m³/h
185 Pa
227 Pa
36 %
51 %

Sounds

Lw
LwA
72.4 dB
69.3 dB(A)
59.4 dB
50.5 dB(A)
63.3 dB
52.9 dB(A)
68.7 dB
65.5 dB(A)

Unit information

Ø 250 mm
1510 mm
720 mm
707 mm
130 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P04 301 0106
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
1098 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
83.6 %
EN308

Fluid coil W

35/25 °C
internal
13.0 °C / 37 %RH
18.0 °C / 26 %RH
0.020 l/s / 0.3 kPa
35  / 25 °C
Water
R213, kvs 4.00
DN15, TR24-SR
1.36 kW

Annual

Camborne,
Great Britain
81.3 %
21 439 kWh
1 kWh

Ecodesign

862 W/(m³/s)
1595 W/(m³/s)
1315 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
83.6 %
EN308

Fluid coil W

35/25 °C
internal
23.5 °C / 58 %RH