Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Pingvin XL eAir W right

Supply
Extract
41 %
41 %
171 m³/h
180 m³/h
50 Pa
50 Pa
19 W
18 W
0.74 kW/(m³/s)
408 m³/h
441 m³/h
285 Pa
301 Pa
139 %
145 %

Sounds

Lw
LwA
46.8 dB
37.7 dB(A)
33.7 dB(A)
30.7 dB(A)
67.7 dB
59.7 dB(A)
58.7 dB
48.2 dB(A)
59.5 dB
48.0 dB(A)
67.5 dB
58.9 dB(A)

Unit information

Ø 160 mm
780 mm
540 mm
555 mm
63 kg
Supply: F7, ePM1 55 %, cassette
Extract: M5, ePM10 75 %, cassette
Right
P10 203 0006
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
353 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 29 %RH
92.1 %
EN308

Fluid coil W

35/25 °C
duct Ø200
13.0 °C / 40 %RH
18.0 °C / 28 %RH
0.004 l/s / 0.2 kPa
35  / 25 °C
Water
R209, kvs 0.63
DN15, TR24-SR
0.28 kW

Annual

Camborne,
Great Britain
90.0 %
4 980 kWh
0 kWh

Ecodesign

428 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.2 °C / 59 %RH
92.1 %
EN308

Fluid coil W

35/25 °C
duct Ø200
23.2 °C / 59 %RH