Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

LTR-7 eAir W-CG

This model was replaced by LTR-7 Z on 2020-03-01
Supply
Extract
69 %
63 %
766 m³/h
806 m³/h
100 Pa
100 Pa
198 W
170 W
1.64 kW/(m³/s)
1041 m³/h
1214 m³/h
185 Pa
227 Pa
36 %
51 %

Sounds

Lw
LwA
75.9 dB
73.6 dB(A)
62.2 dB
54.3 dB(A)
64.8 dB
55.9 dB(A)
73.0 dB
70.2 dB(A)

Unit information

Ø 250 mm
1510 mm
720 mm
707 mm
130 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P04 211 0007
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
Coil: G1/2” (external thread)
1053 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
84.2 %
EN308

Fluid coil W

35/25 °C
internal
13.0 °C / 37 %RH
18.0 °C / 26 %RH
0.022 l/s / 0.7 kPa
35  / 25 °C
Water
R212, kvs 2.50
DN15, TR24-SR
1.29 kW

Fluid coil CG

7/12 °C
duct Ø250
18.0 °C / 26 %RH

Annual

Camborne,
Great Britain
82.0 %
20 336 kWh
1 kWh

Ecodesign

934 W/(m³/s)
1617 W/(m³/s)
1337 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
84.2 %
EN308

Fluid coil W

35/25 °C
internal
23.5 °C / 58 %RH

Fluid coil CG

7/12 °C
duct Ø250
15.7 °C / 87 %RH
0.130 l/s / 9.9 kPa
5  / 10 °C
Water
R313, kvs 4.00
DN15, TR24-SR
2.04 kW / 2.62 kW
1.87 kW
0.78 l/h