Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

Pegasos Z RL E-CG

Supply
Extract
71 %
72 %
903 m³/h
950 m³/h
100 Pa
100 Pa
169 W
173 W
1.30 kW/(m³/s)
1266 m³/h
1305 m³/h
197 Pa
189 Pa
40 %
37 %

Sounds

Lw
LwA
63.9 dB
56.6 dB(A)
52.6 dB(A)
49.6 dB(A)
81.3 dB
73.8 dB(A)
73.5 dB
60.7 dB(A)
72.9 dB
60.3 dB(A)
86.4 dB
80.6 dB(A)

Unit information

Ø 250 mm
1250 mm
1400 mm
677 mm
203 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
400 V/50 Hz, 3~, 3C16A
Unit: 1/4” (internal thread) & DN32
4805 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
82.4 %
EN308

Electric heater E

4000 W internal
18.0 °C / 27 %RH

Fluid coil CG

7/12 °C
internal
18.0 °C / 27 %RH

Annual

Camborne,
Great Britain
80.1 %
23 425 kWh
5 kWh

Ecodesign

783 W/(m³/s)
1555 W/(m³/s)
1275 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH

Electric heater E

4000 W internal
26.0 °C / 50 %RH

Fluid coil CG

7/12 °C
internal
16.1 °C / 84 %RH
0.187 l/s / 4.7 kPa
5  / 10 °C
Water
R317, kvs 4.00
DN20, TR24-SR
3.03 kW / 3.79 kW
2.06 kW
0.99 l/h