Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Pegasos Z eWind W

Supply
Extract
71 %
72 %
903 m³/h
950 m³/h
100 Pa
100 Pa
168 W
173 W
1.29 kW/(m³/s)
1267 m³/h
1305 m³/h
197 Pa
189 Pa
40 %
37 %

Sounds

Lw
LwA
63.9 dB
56.6 dB(A)
52.6 dB(A)
49.6 dB(A)
81.3 dB
73.8 dB(A)
73.5 dB
60.7 dB(A)
72.9 dB
60.3 dB(A)
86.4 dB
80.6 dB(A)

Unit information

Ø 250 mm
1250 mm
1400 mm
677 mm
203 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
808 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
82.4 %
EN308

Fluid coil W

35/25 °C
internal
13.0 °C / 37 %RH
18.0 °C / 26 %RH
0.022 l/s / 0.3 kPa
35  / 25 °C
Water
R213, kvs 4.00
DN15, TR24-SR
1.51 kW

Annual

Camborne,
Great Britain
80.1 %
23 425 kWh
5 kWh

Ecodesign

780 W/(m³/s)
1555 W/(m³/s)
1275 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
82.4 %
EN308

Fluid coil W

35/25 °C
internal
23.5 °C / 58 %RH