Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Cooling

°C
°C
°C

Pelican eWind E-CG

This model was replaced by Pelican Z on 2020-02-29
Supply
Extract
71 %
59 %
300 m³/h
316 m³/h
50 Pa
50 Pa
63 W
43 W
1.21 kW/(m³/s)
478 m³/h
597 m³/h
127 Pa
179 Pa
59 %
89 %

Sounds

Lw
LwA
59.8 dB
43.4 dB(A)
39.4 dB(A)
36.4 dB(A)
67.6 dB
65.3 dB(A)
51.6 dB
41.8 dB(A)
57.6 dB
49.3 dB(A)
64.9 dB
61.7 dB(A)

Unit information

Ø 200 mm
998 mm
1270 mm
590 mm
125 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P05 301 0003
230 V/50 Hz, 1~, 1B16A
Unit: 1/4” (internal thread) & DN32
2348 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 28 %RH
90.3 %
EN308

Electric heater E

2000 W internal
18.0 °C / 28 %RH

Fluid coil CG

7/12 °C
internal
18.0 °C / 28 %RH

Annual

Camborne,
Great Britain
88.1 %
8 561 kWh
0 kWh

Ecodesign

753 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.3 °C / 59 %RH
90.3 %
EN308

Electric heater E

2000 W internal
23.3 °C / 59 %RH

Fluid coil CG

7/12 °C
internal
15.0 °C / 89 %RH
0.033 l/s / 0.9 kPa
5  / 10 °C
Water
R313, kvs 4.00
DN15, TR24-SR
0.85 kW / 1.13 kW
0.80 kW
0.38 l/h