Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

Pelican eAir E

This model was replaced by Pelican Z on 2020-02-29
Supply
Extract
81 %
68 %
428 m³/h
451 m³/h
50 Pa
50 Pa
100 W
70 W
1.36 kW/(m³/s)
555 m³/h
678 m³/h
84 Pa
113 Pa
30 %
50 %

Sounds

Lw
LwA
62.5 dB
46.6 dB(A)
42.6 dB(A)
39.6 dB(A)
70.7 dB
68.5 dB(A)
55.2 dB
45.4 dB(A)
60.7 dB
52.3 dB(A)
68.2 dB
65.3 dB(A)

Unit information

Ø 200 mm
998 mm
1270 mm
590 mm
125 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P05 211 0002
230 V/50 Hz, 1~, 1B16A
Unit: 1/4” (internal thread)
2353 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
87.8 %
EN308

Electric heater E

2000 W internal
18.0 °C / 27 %RH

Annual

Camborne,
Great Britain
85.6 %
11 864 kWh
0 kWh

Ecodesign

960 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.4 °C / 59 %RH
87.8 %
EN308

Electric heater E

2000 W internal
23.4 °C / 59 %RH