Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Pelican eWind W

This model was replaced by Pelican Z on 2020-02-29
Supply
Extract
83 %
68 %
428 m³/h
451 m³/h
50 Pa
50 Pa
107 W
70 W
1.41 kW/(m³/s)
529 m³/h
678 m³/h
76 Pa
113 Pa
23 %
50 %

Sounds

Lw
LwA
62.8 dB
47.0 dB(A)
43.0 dB(A)
40.0 dB(A)
71.1 dB
68.9 dB(A)
55.2 dB
45.4 dB(A)
61.2 dB
52.9 dB(A)
68.2 dB
65.3 dB(A)

Unit information

Ø 200 mm
998 mm
1270 mm
590 mm
125 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P05 301 0006
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
348 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
87.8 %
EN308

Fluid coil W

30/20 °C
internal
13.0 °C / 37 %RH
18.0 °C / 26 %RH
0.010 l/s / 0.7 kPa
35  / 25 °C
Water
R211, kvs 1.60
DN15, TR24-SR
0.71 kW

Annual

Camborne,
Great Britain
85.6 %
11 864 kWh
0 kWh

Ecodesign

1003 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.4 °C / 59 %RH
87.8 %
EN308

Fluid coil W

30/20 °C
internal
23.4 °C / 59 %RH