Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Pegasos XL eAir W

This model was replaced by Pegasos Z on 2020-05-01
Supply
Extract
66 %
60 %
814 m³/h
857 m³/h
100 Pa
100 Pa
229 W
152 W
1.60 kW/(m³/s)
1116 m³/h
1313 m³/h
188 Pa
235 Pa
37 %
53 %

Sounds

Lw
LwA
65.4 dB
51.5 dB(A)
47.5 dB(A)
44.5 dB(A)
68.2 dB
60.6 dB(A)
55.9 dB
47.0 dB(A)
60.6 dB
53.5 dB(A)
70.6 dB
68.4 dB(A)

Unit information

Ø 250 mm
1250 mm
1400 mm
677 mm
203 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P06 211 0106
230 V/50 Hz, 1~, 1B10A
Unit: 1/4” (internal thread)
1103 W

DWG

Winter

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
83.6 %
EN308

Fluid coil W

35/25 °C
internal
13.0 °C / 37 %RH
18.0 °C / 26 %RH
0.019 l/s / 0.2 kPa
35  / 25 °C
Water
R213, kvs 4.00
DN15, TR24-SR
1.36 kW

Annual

Camborne,
Great Britain
81.3 %
21 439 kWh
1 kWh

Ecodesign

955 W/(m³/s)
1595 W/(m³/s)
1315 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
83.6 %
EN308

Fluid coil W

35/25 °C
internal
23.5 °C / 58 %RH