Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C
°C
°C
°C

Summer

°C
%RH
°C
%RH

Cooling

g/kg
°C
°C

Pallas TCG-W

Supply
Extract
49 %
48 %
1676 m³/h
1764 m³/h
100 Pa
100 Pa
258 W
272 W
1.08 kW/(m³/s)
3013 m³/h
3133 m³/h
323 Pa
315 Pa
80 %
78 %

Sounds

Lw
LwA
66.2 dB
57.0 dB(A)
53.0 dB(A)
50.0 dB(A)
71.3 dB
68.4 dB(A)
62.7 dB
52.5 dB(A)
59.5 dB
50.5 dB(A)
72.1 dB
69.4 dB(A)

Unit information

Ø 400 mm
1800 mm
1610 mm
890 mm
450 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P12 211 0012
400 V/50 Hz, 3~, 3B10A
Unit: DN32 & DN32
2013 W

DWG

Winter

TwinCoil

1007623
internal
22.0 °C / 30 %RH
22.0 °C / 30 %RH

Heat Exchanger

Standard
0 °C / 90 %RH
18.0 °C / 27 %RH
82.8 %
EN308

Fluid coil CG

1007623
internal
18.0 °C / 27 %RH
3.4 g/kg

Fluid coil W

35/25 °C
internal
13.0 °C / 37 %RH
18.0 °C / 26 %RH
0.039 l/s / 0.5 kPa
35  / 25 °C
Water
R222, kvs 6.30
DN25, TR24-SR
2.79 kW

Annual

Camborne,
Great Britain
80.5 %
43 705 kWh
6 kWh

Ecodesign

561 W/(m³/s)
1533 W/(m³/s)
1253 W/(m³/s)

Summer

TwinCoil

1007623
internal
23.0 °C / 40 %RH
15.0 °C / 64 %RH
0.223 l/s / 4.7 kPa
5  / 10 °C
Water
R323, kvs 10.00
DN25, TR24-SR
4.85 kW / 5.26 kW
0.50 l/h

Heat Exchanger

Standard
26 °C / 50 %RH
16.9 °C / 87 %RH
82.8 %
EN308

Fluid coil CG

1007623
internal
14.8 °C / 96 %RH
10.0 g/kg
0.050 l/s / 1.0 kPa
5  / 10 °C
Water
R323, kvs 10.00
DN25, TR24-SR
1.18 kW / 1.85 kW
4.57 kW
0.92 l/h

Fluid coil W

35/25 °C
internal
14.8 °C / 96 %RH